Permanent Galvanized Stay in Place Concrete Forming System
Applications for OCM Mesh Form are: Pedestal Foundations; Retaining Walls; Steel Tower Foundations; Wind Force Power Generator Foundations; Under- ground beams, footings, pressure–proof panels, concrete stoppers, mat foundations and all concrete structures constructed on the ground.
Sheet Size |
27” x 97” |
Surface |
18 Sq Ft/Sheet |
Pallet/Ordering |
250 Sheets/4500 Sq Ft per Skid |
V–Ribs 8 per Sheet and 3/4” Deep and 3 7/8” on Center |
|
Tie Wire Spacing |
6” |
Support Spacing (20” High Pour) |
24” at 210 psf |
Sheet Thickness |
26 Ga (0.0217 Inch, Including Galvanizing) |
Weight per Sq Ft |
0.66 lbs |
Weight per Sheet |
11.90 lbs per Sheet |
Installation Notes
OCM Mesh Form rule of thumb is to brace Mesh Form like you would a piece of plywood.
The use of rebar, strongbacks, walers, kickers, etc. (location, size and spacing) is similar to that for con- ventional forming methods per ACI 347, Guide to Formwork for Concrete.
Notes
- 4”-8” minimum lap between running OCM Mesh Form sheets.
- 2-rib minimum lap between stacked OCM Mesh Form sheets.
- Tie wire around rib and bracing is recommended.
- Bracing where sheets lap is also recommended.
- Attach OCM Mesh Form to bracing with wire, Staples, roofing nails or similar.
- North ribs to make 90 degree turns; ribs face into the concrete pour.
- Cut OCM Mesh Form sheets with a grinder, Cutoff saw, abrasive blade or tin snips.